CART

Please share your feedback and help us improve!

Oldham, Gas Leak Detector, Addressable, OLCT 10 N (16997)

Availability : Out of stock
SKU
Oldham, Gas Leak Detector, Addressable, OLCT 10 N (16997)
Key Information:
  • Digital transmitter without display
  • ATEX Approved
  • Detects combustible, toxic gases and O2
  • For use only with the MX43 controller

Descriptions: "The OLCT 10N is the ideal solution for safe areas or Zone 2 ATEX locations"
KEY FEATURES
  • Digital transmitter without display
  • ATEX Approved
  • Detects combustible, toxic gases and O2
  • For use only with the MX43 controller
For commercial and light industrial applications
The OLCT 10N is a single channel digital detector designed for toxic gases, combustible gases and oxygen.
Simplified Installation Intended for use in coordination with Oldham's MX 43 panel, the OLCT 10N provides a rapid response. With the capability of up to 32 detectors on the same digital line or across 8 lines, the
OLCT 10N is application-driven, solution-oriented
Flexibility and Reduced Maintenance
Non-intrusive operator interface requires only a simple magnetic wand alicwing for one man calbration without opening the enclosure. Al calibration information, such as span reserve, is stored in the MX43
Compliance with Standards
  • ATEX Zone 2
  • IP65 and AM( II 3 GD
Technical Specification
  GENERAL
  • Detection of combustible gases, toxic gases or oxygen
  • Digital technology
  • Non-intrusive calibration
  • Cost savings on wiring installation
PHYSICAL
  • Enclosure material: ABS, UV and shocks resistant
  • Dimensions 118x110x60 mm
  • Output: RS485 Modbus, proprietary protocol
POWER
  • Cable inlet: 2 x M16 cable entries, outer diameter 4-8 mm
  • Consumption @24Vdc:
- Electrochemical sensor: 2.5 mA - Catalytic sensor: 50 mA - CO2 Infrared sensor:

APPROVAL
  • II 3 GD - INERIS 11ATEX3023X - IECEx0029X
  • Ex nA, nC IIC T4 Gc for explosimetric versions/ Ex nA, IIC T4 Gc for others
  • Ex tc IIIC T135°C Dc
  • -20°C<Ta< 55°C
  • Electromagnetic compatibility according to EN50270
  GAS RANGES
  • CH,, C3H8, C4H10, H2, : 0-100 % LEL (-20°C to 55°C)
  • O2 : 0-30 % (-20°C to 50°C)
  • CO : 0-300 ppm / 0-1000 ppm (-20°C to 50°C)
  • H2S : 0-30 ppm /0-100 ppm (-20°C to 50°C)
  • NO : 0-100 ppm / 0-300 ppm (-20°C to 50°C)
  • NO2 : 0-10 ppm / 0-30 ppm (-20°C to 50'C)
  • NH3 : 0-100 ppm / 0-1000 ppm (-20°C to 40°C)

ITEM CODE : (16997)

 
More Information
Write Your Own Review
You're reviewing:Oldham, Gas Leak Detector, Addressable, OLCT 10 N (16997)

SHIPPING POLICY

Sellers incur relatively higher shipping costs on low value items. In such cases, charging a nominal delivery charge helps them offset logistics costs. The delivery charge may be waived off by some Sellers, if you shop with them for a minimum predefined value.

REFUND POLICY

If you purchased your item in store, you can return it to any of our store that stocks the same brand for a refund or exchange, subject to our Returns Policy.
CUSTOMERS ALSO VIEWED
YOU MAY ALSO LIKE OUR ENGINEERING SERVICES
We offer design, installation, testing & commission and maintenance of gas systems for Industrial, Commercial & Residential Projects all over UAE. Kindly send us your inquiries to sales@gasntools.com

Personal Information
Additional